tem | Single data hall module-150 kW | Dual data hall module-300 kW | |
Entire system parameters | Dimensions(H*W*D) | 3600mmX(2438mm/3495mm)X12192mm | |
Total power | ≤150kW | ≤300kW | |
Number of cabinets | 26 (main aisle width ≤ 1.5 m) 28 (main aisle width ≤ 0.9 m) | 52 (main aisle width ≤ 1.5 m) 56 (main aisle width ≤ 0.9 m) | |
Waterproof and dustproof | IP55 | ||
Anti-seismic | GR-63-CORE Zone3/9 intensity (The container) | ||
Temperature range | –20°C to +55°C, –40°C to +45°C (If the temperature is lower than –20°C, thermal insulation at the bottom is required.) | ||
Electrical parameters | Power mode | 380/400/415V 50/60Hz,three-phase, four-wire+PE | |
Surge protection level | Class B,nominal: 30kA(8/20µs),maximum: 60kA(8/20µs) | ||
Power System | UPS5000E-200kVA (Full kit in 1+1 redundancy) | UPS5000E-200kVA (Full kit in 1+1 redundancy)*2 | |
Battery Backup Time | Single-route 15 min at full load(SmartLi) | ||
Cooling Parameters | Cooling System | NetCol8000-A055D(In room DX, 3+1 redundancy) | NetCol8000-A055D(In room DX, 7+1 redundancy) |
Continuous power supply to cooling devices | 15 min at full load | ||
Aisle containment | Hot aisle containment | ||
Fire extinguishing parameters | Fire extinguishing system | Automatic gas fire extinguishing, CE edition, non-addressable | |
Fire extinguishing gas | HFC227-ea |