Huawei IDS2000-S Small Modular Data Center

To meet the requirements of quick deployment for the indoor data centers of enterprise branches, Huawei has launched the IDS2000-S modular data center solution which is at the end of the date center network and plays an important role for terminal business.
IDS2000-S adopts All-In-Rack design and features fast deployment, flexible expansion, energy saving and intelligent monitoring.
As an integrative solution, it is designed for the room area of 20 ㎡. IDS2000-S integrates cabinet system, power supply and distribution system, cooling system, monitoring system and cabling system. It can support 1 to 3 cabinets with the total maximum power capacity of 4.5 kW.

Product Features

Highly integration, plug and play

  • All subsystems including the cabinet, monitor, power supply, battery, network connection and etc are integrated in one rack.
  • Pre-engineering design, plug and play.
  • No engineering survey and consultation, fast deployment.

Standard architecture, flexible expansion

  • Adopts modular design, and the configurations are scalable so as to meet different application scenarios.
  • Standard architecture including power supply, heat dissipation and monitor meets fast bulk copy.

Safe, reliable and intelligent management

  • Redundancy design, safe and reliable in key systems such as power distribution system and cooling system and if one fails, the rest still support the normal operation for safe and reliable.
  • Comprehensive monitoring system supports remote management with SMS notification of real-time alarm information and achieves unified management of the global mini data center branches. Monitoring can save the O&M cost to meet unattended operation.

 

Product Specification

Basic type

The basic type of IDS2000-S is mainly used in ordinary buildings with ventilation function and the ambient temperature is between 5 and 30 degrees.

Items

Specifications

Single cabinet dimensions (H*W*D)

2000mm*600mm*1100mm

IT rated power

IT rated power≤4.5kW

Power supply

220V230V240V/50(60)Hz208V(double live wire)/50(60)Hz

External interface

Local standard power interface

Operation condition

Temperature of 5 to 30, relative humidity of 10% to 90%, altitude of 0m to 3000m

Structure

Single front door and double rear doors with 110 degree Opening angle

Heat dissipation

The speed of intelligent fans at top of the cabinet is adjusted in real time according to the temperature in order to save energy.

Air flow

70% door open ratio, Front-back air flow pattern, Optional cooling module at the top of cabinet

Power distribution

Various efficient UPSs with different backup time for option, C-class lightning protection and manual maintenance bypass UPS

Monitoring system

Running information collection and management of cabinet microenvironment, UPS, power distribution equipment and fan control system, supporting remote management and unified control with SMS notification.

Installation type

Coupled with wheels and leveling feet

Air-conditioning type

The air-conditioning type of IDS2000-S is mainly used in the hot area of ordinary buildings and the ambient temperature is between 5 and 45 degrees.

Items

Specifications

Single cabinet dimensions (H*W*D)

2000mm*600mm*1200mm

IT rated power

IT rated power≤5.0kW

Power supply

220V230V240V/50Hz

External interface

Local standard power interface

Operation condition

Temperature of 5 to 45, relative humidity of 20% to 90%, altitude of 0m to 3000m

structure

The top of front door is sealed with glass, and the bottom is perforated, rear doors are double perforated.

Heat dissipation

Intelligent air conditioner automatically runs between fan and compressor mode according to the ambient temperature for energy saving.

Air flow

Professional air guide components at the bottom of the front and rear doors to meet precision cooling.

Power distribution

Various efficient UPSs with different backup time are optional.

Monitoring system

Running information collection and management of cabinet microenvironment, UPS, power distribution equipment and fan control system, supporting remote management and unified control with SMS notification.

Installation type

Coupled with wheels and leveling feet

Low-noise type

The low-noise type of IDS2000-S is mainly used in ordinary buildings with certain ventilation conditions and the ambient temperature is between 5 and 30 ℃ to meet the low-noise requirement. It can be deployed close to the office staff.

Items

Specifications

Single cabinet dimensions (H*W*D)

1200mm*600mm*900mm

IT rated power

IT rated power≤2.4kW

Power supply

220V, 230V, 240V/50(60)Hz

External interface

Local standard power interface

Operation condition

Temperature of 5 to 30, relative humidity of 10% to 90%

Structure

The top of front door is sealed with glass, and the bottom is perforated, rear doors are double perforated.

Heat dissipation

The speed of intelligent fans on top of the cabinet is adjusted in real time according to the temperature in order to save energy.

Air flow

Professional air guide components at the bottom of the front and rear doors to meet precision cooling.

Power distribution

Various optional efficient UPSs with different backup time

Monitoring system

Running information collection and management of cabinet microenvironment, UPS, power distribution equipment and fan control system, supporting remote management and unified control with SMS notification.

Installation type

Coupled with wheels and leveling feet

 

For more details, please refer to Huawei IDS2000-S Small Modular Data Center Solution Brochure (PDF).

Configuration

Typical configurations of the IDS2000-S basic type are as followed.

Typical Configuration

Main Cabinet User Space

Network Cabling Cabinet User Space

Battery Cabinet

UPS

Battery Backup Time

Main Cabinet with UPS

25U

×

×

30min

Main Cabinet without UPS

37U

×

×

×

×

Main Cabinet with UPS + Network Cabling Cabinet

25U

42U

×

30min

Main Cabinet without UPS + Network Cabling Cabinet

37U

42U

×

×

×

Main Cabinet with UPS* + Battery Cabinet

31U

×

30min/1h/2h/4h/8h optional

Main Cabinet with UPS * + Network Cabling Cabinet + Battery Cabinet

31U

42U

30min/1h/2h/4h/8h optional

Note:

* For the configuration, UPS backup is 1+1.

"× "stands for no configuration, "√" stands for standard configuration. Switch, router or sever are not mandatory, and will be provided by customers.

All above six configurations are designed based on condition of the maximum heat emission (3kW).

Main cabinet standard configuration: One set of PDU, monitoring module, smoke detector, temperature and humidity sensor, water sensor, door magnetic switch.

Network cabling cabinet standard configuration: One set of PDU, smoke detector and door magnetic switch.

Battery cabinet standard configuration: One set of smoke detector and door magnetic switch.