To meet the requirements of quick deployment for the
indoor data centers of enterprise branches, Huawei
has launched the IDS2000-S modular data center
solution which is at the end of the date center
network and plays an important role for terminal
business.
IDS2000-S adopts All-In-Rack design and features
fast deployment, flexible expansion, energy saving
and intelligent monitoring.
As an integrative solution, it is designed for the
room area of 20 ㎡. IDS2000-S integrates cabinet
system, power supply and distribution system,
cooling system, monitoring system and cabling
system. It can support 1 to 3 cabinets with the
total maximum power capacity of 4.5 kW.
The basic type of IDS2000-S is mainly used in ordinary buildings with ventilation function and the ambient temperature is between 5 and 30 degrees.
Items
|
Specifications
|
Single cabinet dimensions (H*W*D) |
2000mm*600mm*1100mm |
IT rated power |
IT rated power≤4.5kW |
Power supply |
220V、230V、240V/50(60)Hz;208V(double
live wire)/50(60)Hz |
External interface |
Local standard power interface |
Operation condition |
Temperature of 5℃
to 30℃,
relative humidity of 10% to 90%, altitude of 0m to 3000m |
Structure |
Single front door and double rear doors with 110 degree
Opening angle |
Heat dissipation |
The speed of intelligent fans at top of the cabinet is
adjusted in real time according to the temperature in order
to save energy. |
Air flow |
70% door open ratio, Front-back air flow pattern, Optional
cooling module at the top of cabinet |
Power distribution |
Various efficient UPSs with different backup time for
option, C-class lightning protection and manual maintenance
bypass
UPS |
Monitoring system |
Running information collection and management of cabinet
microenvironment,
UPS, power distribution
equipment and fan control system, supporting remote
management and unified control with SMS notification. |
Installation type |
Coupled with wheels and leveling feet |
The air-conditioning type of IDS2000-S is mainly used in the hot area of ordinary buildings and the ambient temperature is between 5 and 45 degrees.
Items
|
Specifications
|
Single cabinet dimensions (H*W*D) |
2000mm*600mm*1200mm |
IT rated power |
IT rated power≤5.0kW |
Power supply |
220V、230V、240V/50Hz;
|
External interface |
Local standard power interface |
Operation condition |
Temperature of 5℃
to 45℃,
relative humidity of 20% to 90%, altitude of 0m to 3000m |
structure |
The top of front door is sealed with glass, and the bottom
is perforated, rear doors are double perforated. |
Heat dissipation |
Intelligent air conditioner automatically runs between fan
and compressor mode according to the ambient temperature for
energy saving. |
Air flow |
Professional air guide components at the bottom of the front
and rear doors to meet precision cooling. |
Power distribution |
Various efficient UPSs with different backup time are
optional. |
Monitoring system |
Running information collection and management of cabinet
microenvironment,
UPS, power distribution
equipment and fan control system, supporting remote
management and unified control with SMS notification. |
Installation type |
Coupled with wheels and leveling feet |
The low-noise type of IDS2000-S is mainly used in ordinary buildings with certain ventilation conditions and the ambient temperature is between 5 and 30 ℃ to meet the low-noise requirement. It can be deployed close to the office staff.
Items
|
Specifications
|
Single cabinet dimensions (H*W*D) |
1200mm*600mm*900mm |
IT rated power |
IT rated power≤2.4kW |
Power supply |
220V, 230V, 240V/50(60)Hz |
External interface |
Local standard power interface |
Operation condition |
Temperature of 5℃
to 30℃,
relative humidity of 10% to 90% |
Structure |
The top of front door is sealed with glass, and the bottom
is perforated, rear doors are double perforated. |
Heat dissipation |
The speed of intelligent fans on top of the cabinet is
adjusted in real time according to the temperature in order
to save energy. |
Air flow |
Professional air guide components at the bottom of the front
and rear doors to meet precision cooling. |
Power distribution |
Various optional efficient UPSs with different backup time |
Monitoring system |
Running information collection and management of cabinet
microenvironment,
UPS, power distribution
equipment and fan control system, supporting remote
management and unified control with SMS notification. |
Installation type |
Coupled with wheels and leveling feet |
For more details, please refer to Huawei IDS2000-S Small Modular Data Center Solution Brochure (PDF).
Typical configurations of the IDS2000-S basic type are as followed.
Typical Configuration |
Main Cabinet User Space |
Network Cabling Cabinet User Space |
Battery Cabinet |
UPS
|
Battery Backup Time |
Main Cabinet with
UPS |
25U |
× |
× |
√ |
30min |
Main Cabinet without
UPS |
37U |
× |
× |
× |
× |
Main Cabinet with
UPS + Network Cabling
Cabinet |
25U |
42U |
× |
√ |
30min |
Main Cabinet without
UPS + Network Cabling
Cabinet |
37U |
42U |
× |
× |
× |
Main Cabinet with
UPS* + Battery Cabinet |
31U |
× |
√ |
√ |
30min/1h/2h/4h/8h optional |
Main Cabinet with
UPS * + Network Cabling
Cabinet + Battery Cabinet |
31U |
42U |
√ |
√ |
30min/1h/2h/4h/8h optional |
Note:
* For the configuration, UPS backup is 1+1.
"× "stands for no configuration, "√" stands for standard
configuration. Switch, router or sever are not mandatory, and will
be provided by customers.
All above six configurations are designed based on condition of the
maximum heat emission (3kW).
Main cabinet standard configuration: One set of PDU, monitoring
module, smoke detector, temperature and humidity sensor, water
sensor, door magnetic switch.
Network cabling cabinet standard configuration: One set of PDU,
smoke detector and door magnetic switch.
Battery cabinet standard configuration: One set of smoke detector
and door magnetic switch.