UPS8000-D-500K is an online sine-wave double-conversion UPS which features high performance. It is designed for large- and medium-sized computer rooms (for example, network computer rooms in the finance, communications, insurance, railway, medical, and mining industries, enterprises, and public institutions), large- and medium-sized industrial equipment (for example, measuring instruments and industrial automation equipment), precision instruments, emergency systems, and lighting systems.
Model
|
UPS8000-D-500K
|
Rated Capacity |
500 kVA/450 kW |
Input |
|
Mains input rated Voltage |
380/400/415 Vac |
Input Voltage Range |
240 Vac-480 Vac,
65% load at 240 Vac |
Mains input Wiring |
3Ph |
Input Frequency Range |
45-65 Hz |
Total Harmonic Distortion |
THDi<3% |
Input
Power Factor |
0.99 |
Bypass Rated Voltage |
380/400/415 Vac |
Bypass input Wiring |
3Ph+N |
Bypass Input Frequency Range |
50/60 Hz ±2% (±1%-±6% adjustable) |
Battery Voltage |
480 V |
Output |
|
Output Wiring |
3Ph+N |
Rated Voltage |
380/400/415 Vac±1% |
Output Frequency |
Be synchronized to the bypass input (Online Mode), 50/60
Hz±0.05% (Battery Mode) |
Waveform |
Sine wave, THDv<2%(linear load), THDv<3%(100% non-linear
load) |
Output
Power Factor |
0.9 |
Output Imbalance |
Voltage imbalance:±1%; Phase imbalance:±1° |
Efficiency |
Up to 94% |
Switch time |
0 ms |
Overload Capacity |
110% overload for 60 min, 125% overload for 10 min and 150%
overload for 1 min |
Environment |
|
Operation Temperature |
0
℃-40
℃ |
Storage Temperature |
-25
℃-70
℃ |
Relative Humidity |
0%-95% RH(non-condensing) |
Operation Altitude |
≤1000 m, above 1000 meters, derating of 1% for each 100
meters. The maximum altitude is 4000 meters. |
Audible Noise |
<72dB |
Others |
|
Dimensions (H×W×D) |
1900 mm×2100 mm×1000mm |
Weight |
2525 kg |
Communication Interfaces |
Dry contact, RS232, SNMP, Modbus |
Certificate |
TLC, CE |
For more details, please refer to Huawei Large UPS UPS8000-D Series (200-600kVA) Datasheet (PDF).