Huawei UPS5000E-200K-F200
UPS5000-E-200K-F200 is a high performance
uninterruptible power system which can provide high
efficient and reliable power protection to central
offices or medium data centers in telecommunication,
finance, government, transportation, etc. It
features modular design and can output 40-200 kVA
power protection with rated capacity of 380/400/415
V AC. Benefiting from hot-swap design of key
components that reduces mean time to repair greatly,
the system reliability and availability is well
improved.
Product Features
Stable
- Wide input voltage and frequency
range:138-485Vac, 40-70Hz
- 5kA lighting protection design on input port
to reduce lightning related failure
- Redundant design and hot-swappable
controllers, which improve the stability of the
whole system
- Owing to the redundant fan system, 30% rated
load can be driven even when two fans fail
- High overload capacity: 110% overload for
60min, 125% overload for 10min, and 150%
overload for 1min
Saving
- High AC-AC
efficiency,95%@20%Load,96%@40%Load,high
efficiency at low load rate
- Intelligent hibernation technology to
improve operation efficiency and reduce the UPS
power loss efficiently
- High power density of up to 17.5W/inch3, and
the footprint is only 0.5 square meters
- Front maintenance and installation against
the wall, reducing the maintenance space to 0.5
square meters
- Output PF up to 1 and 25% more load driven
Smart
- Modular design and expansion as required,
avoiding overinvestment when planned
- Maximum 32modules paralleled together, and
easy to construct the dual-bus system and N+X
system
- Adjustable battery number from 30 to 40,
which facilitates maintenance
- Built-in SNMP card and Huawei Neteco 1000
software, easy to manage remotely
- Various optional components to meet
customized demands
Simple
- Hot swappable power modules, control
modules, and bypass modules and module
replacement time close to 0, which facilitates
capacity expansion and maintenance
- Self-load test function to enable UPS5000-E
to debug without loads and put into operation
quickly
- The 7-inch colored LCD in standard
configurations supporting graphic display and
various display languages
Product Specification
Model
|
UPS5000-E-200K-F200
|
Rated capacity
|
40KVA/40KW
|
80KVA/80KW
|
120KVA/120KW
|
160KVA/160KW
|
200KVA/200KW
|
Module contained
|
1
|
2
|
3
|
4
|
5
|
Weight
|
227kg
|
260kg
|
293kg
|
326kg
|
359kg
|
Input
|
Rated input voltage
|
380/400/415Vac
|
Input voltage range
|
138-485Vac;
100%load: 305-485 Vac
|
Input Frequency range
|
40-70Hz
|
Input wiring
|
3Ph + N + PE
|
Input power factor
|
0.99
|
THDi
|
THDi < 3% (Linear load); THDi < 5% (Non-linear load)
|
Bypass rated input voltage
|
380/400/415Vac
|
Bypass input wiring
|
3Ph + N + PE
|
Bypass input frequency range
|
50/60Hz±6Hz
|
Synchronization Range
|
50/60Hz±6Hz
|
Battery votage
|
360V-480V (Battery number is adjustable form 30 to 40, 32 in
default )
|
Output
|
Output wiring
|
3Ph + N + PE
|
Output voltage
|
380/400/415Vac±1%
|
Output frequency
|
Be synchronized to the bypass input (Online Mode); 50/60
Hz±0.25% (Battery Mode)
|
THDu
|
100% linear load: THDv < 1%, 100% non-linear load THDv < 3%
|
Output power factor
|
1
|
Voltage phase shift
|
Voltage variation: ±3%; Phase variation: ±1.5°
|
Efficiency
|
96%
|
Switch time
|
0ms
|
Overload capacity
|
Inverter: 110% overload: 60min; 125% overload: 10min; 150%
overload: 1min
Bypass: 135% overload for long term; <1000% overload: 100ms
|
Environment
|
Operating Temperature
|
0℃-40℃
|
Storage Temperature
|
-40℃-70℃
|
Relative Humidity
|
5%-95%RH(Non-condensing)
|
Maximum Operating Altitude
|
<1000m. When the altitude is above 1000 m, the rated
capacity decreases by 1% for each additional 100 m.
|
Audible noise
|
<65dB
|
Others
|
Dimension(height*width*depth)
|
2000×600×850mm
|
Communication
|
Dry contact、RS485、SNMP
|
Certification
|
TLC、CE、CB
|
For more details, please refer to
Huawei Module UPS UPS5000-E Series (40-320kVA) Datasheet (PDF).
Configuration
UPS:
UPS5000-E-200K- F200:contains
40kVA/40kW,80kVA/80kW,120kVA/120kW,160kVA/160kW,200kVA/200kW five
configurations,separately contains 1、2、3、4、5 power
modules,supporting three phase input ,three phase output;
The number of modules and racks accord to the
load power consumption, redundancy needs.
Communication cards:(standard)
Dry contact card:Enables the UPS to manage the
battery system (including the external battery switch and battery
detector), communicate with the PC, provide alarm signals for
external devices, and shut down devices remotely in emergencies.
Monitoring Interface
Card:The monitoring interface cards include the FE port(supporting
SNMP)、RS485(network management port)、Dry contact port.
Battery:
Configuring battery according to the load and
the battery running time
Optional Components:
Parallel Options:
- Parallel cable:The parallel cable connects UPSs in parallel
- BSC cable:The BSC cable transmits bus synchronization
signals in a dual-bus system.
PDC Options:
- Input power distribution cabinet:The input PDC uses one
4-pole 630 A input AC transfer switch (ATS) and two 3-pole 400 A
mould case circuit breakers (MCCBs) respectively for mains and
bypass outputs. The input PDC measures and displays electrical
parameters, such as the three-phase input voltage, current, and
power factor. The input PDC provides dry contacts to report the
status of circuit breakers and a three-phase power indicator to
display the power status.
- Output power distribution cabinet:The output PDC uses two
4-pole 400 A input MCCBs and one 3-pole 630 A maintenance bypass
circuit breaker. The output PDC measures and displays electrical
parameters, such as the three-phase input voltage, current, and
power factor. The output PDC provides dry contacts to report the
status of circuit breakers and a three-phase power indicator to
display the power status.
Other options
- Dry contact extended card: The dry contact extended card
provides extended monitoring ports: five groups of relay output
ports and five groups of input ports. Backfeed protection
card:The backfeed protection card detects mains and bypass
backfeed and provides protection.
- Backfeed protection card: The backfeed protection card
detects mains and bypass backfeed and provides protection.
- Battery switch box: The battery switch box controls the
connection between battery strings and the UPS, and provides
overload and short-circuit protection
- Battery circuit breaker (BCB) box: The BCB box controls the
connection between battery strings and the UPS when multiple
battery strings are connected in parallel.
- Top outlet kit: If you need to install the cabinet against
the wall, install the top outlet kit to meet heat dissipation
requirements.
- IP21 component: The IP21 component prevents water from
dropping into the cabinet, and protects the cabinet to IP21.
- Antiseismic kit: The antiseismic kit reinforces the cabinet
so that the cabinet meets the requirements of 9 degree seismic
fortification intensity.
- Battery detector: The battery detector monitors battery
voltages and temperatures and battery string charge and
discharge currents, and communicates with the PC over Modbus
- Battery grounding failure detector: The battery grounding
failure detector detects battery grounding failures and sends
alarm signals when the ground leakage current exceeds the
specified value.
- Temperature and humidity collection board: Test the
temperature and humidity of UPS.
- Temperature and humidity collection: Test the temperature of
battery room.