Focus on Americas Market
View Quotation Cart ( 0 )
PDU3VN10H50 | ActForNet

MPN: PDU3VN10H50
Category: UPS >> Surge Protection
Vendor: Tripp-Lite
Weight: 27.92 LB(S)
Price: US$ 984.75

-
+
Tripp Lite 3 phase Monitored PDU / Power Distribution Unit offers real-time remote monitoring of voltage, frequency and load levels via built-in network connection. PowerAlert interface supports custom notification of user-specified remote conditions via email, secure web, SNMP, Telnet or SSH interface. PDU output current consumption in amps is displayed per-phase via front panel lighted digital display and can be monitored remotely to warn of potential overloads before critical IT mains breakers trip.

OUTPUT
Output Capacity Details:12.6kVA total 20A per bank (balanced)
Frequency Compatibility:60 Hz
Output Receptacles:(30) C13 (6) C19
Output Nominal Voltage:208V single phase
Overload Protection:3 20A double-pole circuit breakers (1 per output phase)
Outlet Quantity / Type:36 total - 30 C13 (10 per phase), 6 C19 (2 per phase)
Number of Outlets:36
Outlet Type:IEC-C13, IEC-C19

INPUT
PDU Input Voltage:208
Maximum Input Amps:35
PDU Plug Type:HUBBELL CS8365C 50A
Input Cord Length (ft.):10
Input Cord Length (m):3.05
Input Phase:3-Phase

LEDS ALARMS and SWITCHES
Switches:Pushbutton switches enable local display of each phase separately, display rotate and display IP address functions

Front Panel LEDs:2 digit current meter display reports output amps per phase and IP address
Material of Construction:Steel

Form Factors Supported:Vertical rackmount installation supported with included mounting brackets supports tooless mounting in button-mount compatible racks
PDU Form Factor:Vertical (0U)

Certifications
Tested to UL60950-1 (USA, Canada), NOM (Mexico), Class A (Emissions), ROHS, TAA Compliant

Item Dimension (L"xW"xH"):
6.6 x 9.3 x 75.5

Weight:
27.92 lb

Warranty Information:
2-year limited warranty