Feature
- Wide range of AC input voltage from 85V to 300V per phase
- High rectifier efficiency over 96% helps to save energy
- Excellent rectifier dormancy function helps to increase system efficiency
- Wide operation temperature range of rectifier from -40℃ to 75℃
- Rectifier MTBF≥ 500,000 hours
- Online-swappable rectifier provides easy installation and maintenance
- Intelligent battery management and protection helps to prolong battery lifespan
- Anti-reverse connection of battery polarity function
- Support site environment monitoring and remote management through dry contact, serial interface or Ethernet interface
- Intelligent control module with LCD provides visible monitoring
- Thorough alarms and protection against failures
- E- label function provides online equipments management over entire network
- Support installation over standard 19 inch and 21 inch rack
Specification
Type |
ETP4830 |
ETP4890 |
ETP48200 |
System specification |
Dimension |
43.6mm(H) ×442mm(W) ×255mm(D) |
86.1mm(H) ×442mm(W) ×255mm(D) |
266.7mm(H)×482.6mm(W)×310mm(D) |
Weight |
≤8kg (full configured) |
≤10kg (full configured) |
≤25Kg(without rectifiers) |
Rated capacity |
30A (2PSU) |
45/90A (compatible with 15A and 30A rectifier) (3PSU) |
200A(4PSU) |
Cooling mode |
Natural cooling |
Maintenance mode |
Front access maintenance, supporting module-level replacement |
Cabling mode |
Cable outlet from the bottom of the cabinet |
Installation mode |
Installed on 19-inch rack or 21-inch rack, embedded in cabinet |
Protection level |
IP20 |
Environmental specification |
Operating temperature |
-40~+70ºC |
-20~+50℃ |
Operating humidity |
5%~95%(non-condensing) |
Altitude |
0~4000m (at the altitude from 2000m to 4000m, the temperature declines by 1ºC for each increase of 200m in altitude) |
AC distribution |
AC input |
220V single phase/110V dual live wire |
380V three phase/220V single phase/110V dual live wire |
AC output |
N/A |
N/A |
ETP48200-A6: 1x 20A/1P, 2x 16A/1P MCB
ETP48200-B6: 1x 16A/2P MCB |
AC input voltage |
85~300VAC, rated: 220VAC |
AC input frequency |
45~66Hz, rated: 50Hz/60Hz |
SPD for AC input |
N/A |
30/60kA(8/20µs) |
DC distribution |
Output voltage |
-42~-58VDC, default value: -53.5VDC |
maximum output power |
2000W |
4800W |
12000W |
Battery branch |
1x20A fuse |
1×80A MCB |
2x125A MCB |
BLVD |
2x20A fuse |
1×10A MCB, 1×32A MCB, 2×40A MCB |
1x63A MCB, 1x32A MCB, 3x16A MCB |
LLVD |
N/A |
N/A |
ETP48200-A6: 2x100A MCB
ETP48200-B6: 2x100A MCB, 1x20A MCB |
Rectifier module |
Efficiency |
>96% |
Input voltage |
85~300VAC, rated: 220VAC |
Monitoring unit |
Sensors interface |
Gate, water, smoke, battery temperature, environmental temperature & humidity (when configured with convertor box) |
Digital input |
7 branches (configured with converter box) |
6 branches |
Alarm output |
8 branches (configured with converter box) |
8 branches |
Communication port |
RS485/RS232 |
RS485/RS232, FE |
Equipment Configuration
Embedded power includes power rack and rectifiers, signal convertor box, batteries, and sensors.
Power rack: includes AC distribution, DC distribution and monitoring unit.
Rectifier: the capacity of rectifier depends on load and charging current.
Signal convertor box: signal convert box is needed when power needs to configure with sensors for ETP4830 and ETP4890. ETP48200 has been configured with signal interface.
Sensor: battery temperature & humidity sensor, environment temperature & humidity sensor, door switch sensor, smog sensor, water sensor and so on.
Battery: according to load power and backup time to choose battery.