Feature
	- Wide range of AC input voltage from 85V to 300V per phase
- High rectifier efficiency over 96% helps to save energy
- Excellent rectifier dormancy function helps to increase system efficiency
- Wide operation temperature range of rectifier from -40℃ to 75℃
- Rectifier MTBF≥ 500,000 hours
- Online-swappable rectifier provides easy installation and maintenance
- Intelligent battery management and protection helps to prolong battery lifespan
- Anti-reverse connection of battery polarity function
- Support site environment monitoring and remote management through dry contact, serial interface or Ethernet interface
- Intelligent control module with LCD provides visible monitoring
- Thorough alarms and protection against failures
- E- label function provides online equipments management over entire network
- Support installation over standard 19 inch and 21 inch rack
- 
	  
Specification
	
		
			| Type | ETP4830 | ETP4890 | ETP48200 | 
		
			| System specification | Dimension | 43.6mm(H) ×442mm(W) ×255mm(D) | 86.1mm(H) ×442mm(W) ×255mm(D) | 266.7mm(H)×482.6mm(W)×310mm(D) | 
		
			| Weight | ≤8kg (full configured) | ≤10kg (full configured) | ≤25Kg(without rectifiers) | 
		
			| Rated capacity | 30A (2PSU) | 45/90A (compatible with 15A and 30A rectifier) (3PSU) | 200A(4PSU) | 
		
			| Cooling mode | Natural cooling | 
		
			| Maintenance mode | Front access maintenance, supporting module-level replacement | 
		
			| Cabling mode | Cable outlet from the bottom of the cabinet | 
		
			| Installation mode | Installed on 19-inch rack or 21-inch rack, embedded in cabinet | 
		
			| Protection level | IP20 | 
		
			| Environmental specification | Operating temperature | -40~+70ºC | -20~+50℃ | 
		
			| Operating humidity | 5%~95%(non-condensing) | 
		
			| Altitude | 0~4000m (at the altitude from 2000m to 4000m, the temperature declines by 1ºC for each increase of 200m in altitude) | 
		
			| AC distribution | AC input | 220V single phase/110V dual live wire | 380V three phase/220V single phase/110V dual live wire | 
		
			| AC output | N/A | N/A | ETP48200-A6: 1x 20A/1P, 2x 16A/1P MCB ETP48200-B6: 1x 16A/2P MCB
 | 
		
			| AC input voltage | 85~300VAC, rated: 220VAC | 
		
			| AC input frequency | 45~66Hz, rated: 50Hz/60Hz | 
		
			| SPD for AC input | N/A | 30/60kA(8/20µs) | 
		
			| DC distribution | Output voltage | -42~-58VDC, default value: -53.5VDC | 
		
			| maximum output power | 2000W | 4800W | 12000W | 
		
			| Battery branch | 1x20A fuse | 1×80A MCB | 2x125A MCB | 
		
			| BLVD | 2x20A fuse | 1×10A MCB, 1×32A MCB, 2×40A MCB | 1x63A MCB, 1x32A MCB, 3x16A MCB | 
		
			| LLVD | N/A | N/A | ETP48200-A6: 2x100A MCB ETP48200-B6: 2x100A MCB, 1x20A MCB
 | 
		
			| Rectifier module | Efficiency | >96% | 
		
			| Input voltage | 85~300VAC, rated: 220VAC | 
		
			| Monitoring unit | Sensors interface | Gate, water, smoke, battery temperature, environmental temperature & humidity (when configured with convertor box) | 
		
			| Digital input | 7 branches (configured with converter box) | 6 branches | 
		
			| Alarm output | 8 branches (configured with converter box) | 8 branches | 
		
			| Communication port | RS485/RS232 | RS485/RS232, FE | 
	
 
 
Equipment Configuration
Embedded power includes power rack and rectifiers, signal convertor box, batteries, and sensors.
Power rack: includes AC distribution, DC distribution and monitoring unit.
Rectifier: the capacity of rectifier depends on load and charging current.
Signal convertor box: signal convert box is needed when power needs to configure with sensors for ETP4830 and ETP4890. ETP48200 has been configured with signal interface.
Sensor: battery temperature & humidity sensor, environment temperature & humidity sensor, door switch sensor, smog sensor, water sensor and so on.
Battery: according to load power and backup time to choose battery.